Rockwell Automation 20D PowerFlex 700S Phase II Drive Frames 1...6 Installation Instructions User Manual

Page 48

Advertising
background image

48

Rockwell Automation Publication 20D-IN024C-EN-P - July 2013

PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control

Table 16 - 600 Volt AC Input Frames 1…6 Drive Protection Devices

20DD125

5

100

117

97.6

150

250

150

500

375

150

75

90.1

74.9

125

200

125

350

350

125

20DD156

6

125

146.5

121.7

200

350

200

600

450

250

100

131

97.6

175

250

175

500

375

250

20DD180

6

150

169

140.5

225

400

225

600

500

250

125

147

121.7

200

350

200

600

450

250

20DD248

6

200

232.8

188

300

550

300

700

700

400

150

169

140.5

225

400

225

600

500

250

(1)

Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.

(2)

Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(3)

Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(4)

Maximum allowable rating by US NEC. Exact size must be chosen for each installation.

(5)

Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.

(6)

Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.

(7)

Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.

(8)

The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See

Bulletin 140M Motor Protection Circuit Breakers Application Ratings

.

(9)

When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal considerations may require a larger
enclosure.

Drive Cat.
No.

Fr

am

e

HP Rating

Input Ratings

Dual Element
Time Delay Fuse

Non-Time Delay
Fuse

Circuit
Breaker

(3)

Motor
Circuit
Protector

(5)

140M Motor Starter with Adjustable Current Range

(6)(7)

ND

HD

Amps

kVA

Min

(1)

Max

(2)

Min

(3)

Max

(4)

Max

(4)

Max

(6)

Available Cat. No.s

(8)

Minimum Enclosure
Volume (in.

3

)

(9)

Drive
Cat. No.

Fr

am

e

HP Rating

Input Ratings

Dual Element
Time Delay Fuse

Non-Time Delay
Fuse

Circuit
Breaker

(3)

Motor
Circuit
Protector

(5)

140M Motor Starter with Adjustable Current Range

(6)(7)

ND

HD

Amps

kVA

Min

(1)

Max

(2)

Min

(3)

Max

(4)

Max

(4)

Max

(6)

Available Cat. No.s

(8)

Minimum Enclosure
Volume (in.

3

)

(9)

20DE1P7

1

1

0.75

1.3

1.4

2

4

2

6

15

3

M-C2E-B16

7269

20DE2P7

1

2

1.5

2.1

2.1

3

6

3

10

15

3

M-C2E-B25

7269

20DE3P9

1

3

2

3.0

3.1

6

9

6

15

15

7

M-C2E-B40

M-D8E-B40

7269

20DE6P1

1

5

3

5.3

5.5

9

12

9

20

20

15

M-D8E-B63

7269

20DE9P0

1

7.5

5

7.8

8.1

10

20

10

35

30

15

M-D8E-C10

M-F8E-C10

7269

20DE011

1

10

7.5

9.9

10.2

15

25

15

40

40

15

M-D8E-C10

M-F8E-C10

7269

20DE017

1

15

10

15.4

16.0

20

40

20

60

50

20

M-D8E-C16

M-F8E-C16

7269

20DE022

2

20

15

20.2

21.0

30

50

30

80

80

30

M-F8E-C25

7269

20DE027

2

25

20

24.8

25.7

35

60

35

100

100

50

M-F8E-C25

7269

20DE032

3

30

25

29.4

30.5

40

70

40

125

125

50

M-F8E-C32

13630

20DE041

3

40

30

37.6

39.1

50

90

50

150

150

100

20DE052

3

50

40

47.7

49.6

60

110

60

200

200

100

20DE062

4

60

50

58.2

60.5

80

125

80

225

225

100

20DE077

5

75

72.3

75.1

90

150

90

300

300

100

60

58.2

60.5

90

125

90

250

250

100

20DE099

5

100

92.9

96.6

125

200

125

375

375

150

75

72.3

75.1

100

175

100

300

300

100

20DE125

6

125

117

121.6

150

250

150

375

375

250

100

93

96.6

125

200

125

375

375

150

20DE144

6

150

135

140.5

175

300

175

400

400

250

125

117

121.6

150

275

150

375

375

250

(1)

Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.

(2)

Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(3)

Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(4)

Maximum allowable rating by US NEC. Exact size must be chosen for each installation.

(5)

Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.

(6)

Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.

(7)

Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.

(8)

The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See

Bulletin 140M Motor Protection Circuit Breakers Application Ratings

.

(9)

When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal considerations may require a larger
enclosure.