Table 2 – Rockwell Automation 20-750-PBUS Profibus DPV1 Option Module User Manual

Page 26

Advertising
background image

26

Rockwell Automation Publication 750COM-UM004B-EN-P - September 2012

Chapter 2 Installing the Option Module

Table 2 - Drive and Option Module Start-Up Status Indications

After verifying correct operation, swing down the drive HIM bezel to its closed
position and install the drive cover. For more details on status indicator
operation, see

page 66

and

page 67

.

Item Name

Color

State

Description

Drive STS Indicator

STS
(Status)

Green

Flashing

Drive ready but not running, and no faults are present.

Steady

Drive running, no faults are present.

Yellow

Flashing

When running, a type 2 (non-configurable) alarm condition exists – drive
continues to run. When stopped, a start inhibit condition exists and the
drive cannot be started (see drive parameter 933 - [Start Inhibits]).

Steady

A type 1 (user configurable) alarm condition exists, but the drive
continues to run.

Red

Flashing

A major fault has occurred. Drive will stop. Drive cannot be started until
fault condition is cleared.

Steady

A non-resettable fault has occurred.

Red/Yellow

Flashing
Alternately

A minor fault has occurred. Use drive parameter 950 - [Minor Flt Config]
to enable. If not enabled, acts like a major fault. When running, the drive
continues to run. System is brought to a stop under system control. The
fault must be cleared to continue.

Yellow/Green

Flashing
Alternately

When running, a type 1 alarm exists.

Green/Red

Flashing
Alternately

Drive is updating.

Option Module Status Indicators

PORT

Off

The option module is not powered or connected properly to the drive.

Red

Flashing

The option module is not receiving any communication from drive.

Steady

The option module detected a duplicate or invalid port ID.

Green

Flashing

The option module is establishing communication with drive.

Steady

The option module is properly connected and communicating with drive.

Orange

Steady

The drive to which option module is connected is not an Allen-Bradley
brand.

MOD

Off

The option module is not powered or connected properly to the drive.

Red

Flashing

The option module has failed the firmware test or firmware update is in
progress.

Steady

The option module has failed the hardware test.

Green

Flashing

The option module is operational but is not transferring I/O data.

Steady

The option module is operational and is transferring I/O data.

NET A

Off

The option module cannot establish network communication or has
experienced a Communication Timeout.

Red

Flashing

The option module has detected a Network Configuration Error.

Steady

The option module has experienced an internal network controller error
(Profibus ASIC Self-Test failure).

Green

Steady

The option module is properly connected and communicating over the
Profibus network.

Advertising