76

Rockwell Automation Publication 750COM-UM004B-EN-P - September 2012

Appendix B Option Module Parameters

About Parameter Numbers

Each parameter set is numbered consecutively.

How Parameters Are
Organized

The

Device Parameters and Host Parameters are separately displayed in a

Numbered List

view order.

Device Parameters

Configuration Tool

Numbering Scheme

HIM
Connected Components Workbench

software

DriveExplorer software
DriveExecutive software

The Device parameters and Host parameters begin with
parameter 01. For example, Device Parameter 01 -
[DPI Port]
and Host Parameter 01 - [Net to Drv DL
01]
are Parameter 1 as indicated by this manual.

Acyclic Messaging

See

Chapter 6

,

Acyclic Messaging

.

Parameter

No.

Name & Description

Details

01

[Port Number]
Displays the drive port into which the option
module is installed. Typically, this will be Port 4, 5,
or 6.

Minimum:

0

Maximum:

7

Type:

Read Only

02

[DLs From Net Act]
Displays the number of controller-to-drive
Datalinks that the drive is using based on the I/O
connection opened by the controller.

Minimum:

0

Maximum:

16

Type:

Read Only

03

[DLs To Net Act]
Displays the number of drive-to-controller
Datalinks that the controller is using based on the
I/O connection opened by the controller.

Minimum:

0

Maximum:

16

Type:

Read Only

04

[Net Addr Src]
Displays the source from which the option
module’s node address is taken. This will be the
Node Address switches (see

Figure 1 on page 20

and

Table 1 on page 21

), or the value of Device

Parameter 05 - [Net Addr Cfg].

Values:

0 = Switches
1 = Parameters

Type:

Read Only

05

[Net Addr Cfg]
Sets the network node address for the option
module if Device Parameter 04 - [Net Addr Src]
is set to ‘1’ (Parameters).

Default:

126

Minimum:

0

Maximum:

126

Type:

Read/Write

06

[Net Addr Act]
Displays the actual network node address used by
the option module.

Minimum:

0

Maximum:

126

Type:

Read Only