Rockwell Automation 20-750-PBUS Profibus DPV1 Option Module User Manual

Page 79

Advertising
background image

Rockwell Automation Publication 750COM-UM004B-EN-P - September 2012

79

Option Module Parameters Appendix B

17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

[DL To Net 01]
[DL To Net 02]
[DL To Net 03]
[DL To Net 04]
[DL To Net 05]
[DL To Net 06]
[DL To Net 07]
[DL To Net 08]
[DL To Net 09]
[DL To Net 10]
[DL To Net 11]
[DL To Net 12]
[DL To Net 13]
[DL To Net 14]
[DL To Net 15]
[DL To Net 16]
Sets the port number and parameter number to
which the selected Datalinks should connect. Each
selected port/parameter will be read and their
values transmitted over the network to the
controller. These are parameters read by the
controller (inputs to the controller).

If setting the value manually, the parameter value
= (10000 * port number) + (origination parameter
number). For example, suppose you want to use
Host Parameter 17 - [DL To Net 01] to read
Parameter 02 of an optional I/O module plugged
into drive Port 6. The value for Host Parameter 17
- [DL To Net 01]
would be 60002 [(10000 * 6) + 2].

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Minimum:

0

Maximum:

159999

Type:

Read/Write

Reset Required: No

33

[Comm Flt Action]
Sets the action that the option module and drive
will take if the option module detects that I/O
communication has been disrupted. This setting is
effective only if I/O that controls the drive is
transmitted through the option module. When
communication is re-established, the drive will
automatically receive commands over the network
again.

Default:

0 = Fault

Values:

0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg

Type:

Read/Write

Reset Required: No

Parameter

No

Name & Description

Details

ATTENTION: Risk of injury or equipment damage exists. Host
Parameter 33 - [Comm Flt Action] lets you determine the action of the
option module and connected drive if I/O communication is disrupted. By
default, this parameter faults the drive. You may configure this parameter
so that the drive continues to run, however, precautions should be taken
to verify that the setting of this parameter does not create a risk of injury
or equipment damage. When commissioning the drive, verify that your
system responds correctly to various situations (for example, a
disconnected cable).