Rockwell Automation Publication 750COM-UM004B-EN-P - September 2012

77

Option Module Parameters Appendix B

07

[Reset Module]
No action if set to ‘0’ (Ready). Resets the option
module if set to ‘1’ (Reset Module). Restores the
option module to its factory default settings if set
to ‘2’ (Set Defaults). This parameter is a command.
It will be reset to ‘0’ (Ready) after the command
has been performed.

When performing a Set Defaults, the drive may
detect a conflict. If this occurs, the drive will not
allow a Set Defaults action. You must resolve the
conflict before attempting a Set Defaults action for
the option module.

Default:

0 = Ready

Values:

0 = Ready
1 = Reset Module
2 = Set Defaults

Type:

Read/Write

Reset Required: No

08

[Net Data Format]
Displays the byte alignment for the network data
as selected with the Byte Swap switch 8 (see

Figure 1 on page 20

).

Default:

0 = Ltl Endian

Values:

0 = Ltl Endian
1 = Big Endian

Type:

Read Only

09

[PROFIBUS Mode]
Displays the Profibus operation mode selected by
the user using the mode selection jumper (see

page 11

). This will be either Normal or PROFIdrive.

Important: PROFIdrive is not supported in this
version. It is reserved for future firmware update.

Values:

0 = Normal
1 = PROFIdrive

Type:

Read Only

10

[PROFIBUS Alarms]
Enables or disables generation of alarms on
Profibus.

Default:

0 = Enable

Values:

0 = Enable
1 = Disable

Type:

Read/Write

11

[DPV1 Map Mode]
Enables S7 Controller compatibility.

Default:

0 = Standard

Values:

0 = Standard
1 = S7 Comp

Type:

Read/Write

Parameter

No.

Name & Description

Details

ATTENTION: Risk of injury or equipment damage exists. If the option
module is transmitting I/O that controls the drive, the drive may fault
when you reset the option module. Determine how your drive will
respond before resetting the option module.