Rockwell Automation 20-750-PBUS Profibus DPV1 Option Module User Manual

Page 71

Advertising
background image

Rockwell Automation Publication 750COM-UM004B-EN-P - September 2012

71

Troubleshooting Chapter 7

14

DPI Baud 500kbps

The option module detected that the drive was communicating at 500 Kbps.

15

DPI Host Invalid

The option module was connected to an incompatible product.

16

DPI Dup Port

Another peripheral with the same port number is already in use.

17

DPI Type 0 Logon

The option module has logged in for Type 0 control.

18

DPI Type 0 Time

The option module has not received a Type 0 status message within the specified time.

19

DPI DL Logon

The option module has logged into a Datalink.

20

DPI DL Error

The drive rejected an attempt to log in to a Datalink because the Datalink is not supported or is used by another
peripheral.

21

DPI DL Time

The option module has not received a Datalink message within the specified time.

22

DPI Ctrl Disable

The option module has sent a ‘Soft Control Disable’ command to the drive.

23

DPI Ctrl Enable

The option module has sent a ‘Soft Control Enable’ command to the drive.

24

DPI Msg Timeout

A Client-Server message sent by the option module was not completed within 1 second.

25

DPI Manual Reset

The option module was reset by changing its Reset Module parameter.

SI Events

26

SI Online

The option module has logged into the Serial Interface Communications.

27

SI Logon Error

The option module failed to log into the Serial Interface.

28

SI Comm Fault

The Serial Interface Communications has faulted.

Network Events

29

Net Link Up

A network link was available for the Option Module.

30

Net Link Down

The network link was removed from the Option Module.

31

Net Dup Address

The option module uses the same address as another device on the network.

32

Net Comm Fault

The option module detected a communications fault on the network.

33

Net Sent Reset

The option module received a reset from the network.

34

Net IO Close

An I/O connection from the network to the option module was closed.

35

Net Idle Fault

The option module detected an idle fault condition on the network (Master in programming mode or slave
parameterization in progress).

36

Net IO Open

An I/O connection from the network to the option module has been opened.

37

Net IO Timeout

An I/O connection from the network to the option module has timed out.

38

Net IO Size Err

The option module received an incorrectly sized I/O packet.

39-56

Reserved

57

Option Card Flt

Internal option module faults.

58

Module Defaulted

The option module has been set to defaults.

59

Net Freeze

Freeze command has been issued by the Profibus master for this option module.

60

Net Unfreeze

Unfreeze command has been issued by the Profibus master for this option module.

61

Net Sync

Sync command has been issued by the Profibus master for this option module.

62

Net Unsync

Unsync command has been issued by the Profibus master for this option module.

63

Net Clear Cmd

The option module received a Profibus ‘Clear Command’ from the network master.

64

Net Set Prm

The option module received a Profibus ‘Set Parameters’ command from the network master.

65

Net WD Timeout

The Profibus ASIC has declared a network timeout.

Table 7 - Option Module Events (Continued)

Code

Event Text

Description