Rockwell Automation Publication 520COM-UM004A-EN-E - November 2013

Chapter 2

Installing the Adapter

5.

Align the Communication card-Drive header on the adapter with the
interface connector. Then, press down firmly around the adapter.
The adapter snaps into the back of the control module.

6.

Attach the control module to the power module.

Connecting the Adapter to
the Network

1.

Remove power from the network.

2.

Use static control precautions.

3.

Connect a PROFIBUS connector to the cable.

PROFIBUS connectors are available from a variety of sources and in
various sizes. As such, there may be mechanical limitations that prohibit
the use of some connectors.
Phoenix SUBCON-PLUS-PROFIB/AX/SC (Part #2744380), Siemens
6GK1500-0FC00, or Brad BM5G60PP4Mxxxx are recommended for use
with PowerFlex 520-series drives.

IMPORTANT

The CS1/CS2 terminals on the adapter provide a clean ground for the
communication bus cable shields. You should connect the CS1 or CS2
terminal to a clean ground or PE ground on the drive.

ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain
high voltages that can cause injury or death. Remove power from the drive, and
then verify power has been discharged before connecting the adapter to the
network.