Rockwell Automation Publication 520COM-UM004A-EN-E - November 2013

Appendix B

Adapter Parameters

19

[Reset Module]
No action if set to 0 “Ready”. Resets the adapter if set to 1 “Reset
Module”. Restores the adapter to its factory default settings if
set to 2 “Set Defaults”. This parameter is a command. It will be
reset to 0 “Ready” after the command has been performed.

Default:

0 = Ready

Values:

0 = Ready
1 = Reset Module
2 = Set Defaults

Type:

Read/Write

Reset Required:

No

20

[Profibus Alarms]
Displays the status of alarms on PROFIBUS. It is set with the
PROFIBUS configuration tool and is updated after the Data
Exchange state has been established by the controller to the
adapter.

Values:

0 = Enable
1 = Disable

Type:

Read Only

21

[DPV1 Map Mode]
Enables S7 Controller compatibility to address Acyclic data
access.

Default:

0 = Standard

Values:

0 = Standard
1 = S7 Comp

Type:

Read/Write

Reset Required:

Yes

22

[DSI I/O Act]
Displays the Drives that are active in Multi-drive mode.

Bit Definitions:

0 = Drive Inactive
1 = Drive Active

Digits:

0 = Drive 0 Actv
1 = Drive 1 Actv
2 = Drive 2 Actv
3 = Drive 3 Actv
4 = Drive 4 Actv

Type:

Read Only

Parameter

No.

Name and Description

Details

ATTENTION: Risk of injury or equipment damage exists. If the adapter
is transmitting I/O that controls the drive, the drive may fault when you
reset the adapter. Determine how your drive will respond before
resetting the adapter.

0 = Drive Inactive, 1 = Drive Active

Drive 0 Actv

Digit 1

Drive 1 Actv

Digit 2

Drive 2 Actv

Digit 3

Drive 3 Actv

Digit 4

Drive 4 Actv

Digit 5