Logic Command/Status Words: PowerFlex 520-Series Drives

Position Bit Definitions

Logic Status Word

Velocity Bit Definitions

Comm Logic Command – C122 = 1 “Position”
Logic Bits
15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Command

Description

x

Normal Stop

0 = Not Normal Stop
1 = Normal Stop

x

Start

(1)

(1) A Not Stop condition (logic bit 0 = 0) must first be present before a 1 = Start condition will start the drive.

0 = Not Start
1 = Start

x

Jog 1

(2)

(2) A Not Stop condition (logic bit 0 = 0) must first be present before a 1 = Jog condition will jog the drive. A transition to a “0” will stop

the drive.

0 = Not Jog
1 = Jog

x

Clear Fault

(3)

(3) To perform this command, the value must switch from “0” to “1.”

0 = Not Clear Fault
1 = Clear Fault

x

x

Unipolar Direction

00 = No Command
01 = Forward Command
10 = Reverse Command
11 = No Command

x

Logic Input 1

1 = Logic In 1

x

Logic Input 2

1 = Logic In 2

x

x

x

Frequency and Position
Steps

000 = Frequency and Position Step 0
001 = Frequency and Position Step 1
010 = Frequency and Position Step 2
011 = Frequency and Position Step 3
100 = Frequency and Position Step 4
101 = Frequency and Position Step 5
110 = Frequency and Position Step 6
111 = Frequency and Position Step 7

x

Find Home

1 = Find Home

x

Hold Step

1 = Hold Step

x

Redefine Position

1 = Pos Redefine

x

Enable Sync

1 = Sync Enable

x

Disable Travel

1 = Travel Disable

Comm Logic Status – C122 = 0 “Velocity”
Logic Bits
15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Command

Description

x

Run Ready

0 = Not Ready to Run
1 = Ready to Run

x

Active

0 = Not Active
1 = Active (Running)

x

Command Direction

0 = Reverse
1 = Forward

x

Actual Direction

0 = Rotating Reverse
1 = Rotating Forward

x

Accel

0 = Not Accelerating
1 = Accelerating

x

Decel

0 = Not Decelerating
1 = Decelerating

x

Reserved

x

Fault

0 = Not Faulted
1 = Faulted

x

At Speed

0 = Not at Reference
1 = At Reference

x

Main Frequency

0 = Not Controlled by Active Com
1 = Controlled by Active Com

x

Operation Command

0 = Not Controlled by Active Com
1 = Controlled by Active Com

x

Parameters

0 = Not Locked
1 = Locked

x

Digital Input 1 Status

x

Digital Input 2 Status

x

Digital Input 3 Status

x

Digital Input 4 Status