Configuring the adapter as a slave – Rockwell Automation 25-COMM-P PowerFlex PROFIBUS DPV1 Adapter User Manual
Page 36
![background image](/manuals/578065/36/background.png)
36
Rockwell Automation Publication 520COM-UM004A-EN-E - November 2013
Chapter 4
Configuring the PROFIBUS Master
Configuring the Adapter as a
Slave
Follow these steps to add and configure a 25-COMM-P adapter as a slave.
1.
Drag the Slave icon into the Bus Configuration window.
The slave is added to the PROFIBUS network and configured to the
Master in a networked relationship.
2.
In the treeview, click ‘+’ to expand the slave you added.
The list in the window above shows the possible input/output
configuration values for a 25-COMM-P Slave. The Datalinks (1...4) allow
the assignment of configured drive parameters to be included in the
PROFIBUS DP I/O data frames that are transferred between the
CompactLogix controller and the PowerFlex 520-series drive.
3.
Click on the 25-COMM-P in the Bus Configuration window.