Installing the Adapter

Chapter 2

PROFIBUS Connector

4.

Connect the PROFIBUS cable to the adapter and secure it with the two
screws on the connector.

Network Wiring Diagram

5.

Ground the shield to reduce electrostatic pickup. However, shielding is
only effective when the shield is properly connected to ground. See the
PROFIBUS Installation Guideline for instructions to correctly ground the
shield.

IMPORTANT

PROFIBUS communication may not operate correctly if the cable shield
does not make full contact with the connector housing.

Terminal

Signal

Function

Housing

Shield

Bus cable shield (outer screen that surrounds A and B conductors)

1

Not connected

2

Not connected

3

B-LINE

Positive RxD/TxD according to RS485 specification

4

RTS

Request to send

5

GND BUS

Network Zero Volt Reference (isolated from drive side)

6

+5V BUS

+5V output to network (isolated from drive side)

7

Not connected

8

A-LINE

Negative RxD/TxD according to RS485 specification

9

Not connected

B

A

B

A

B

A

B

A

A

B

A

B