Changing the Fault Action

Set the values of

Device parameters 11 [Comm Flt Action] and 12 [Idle Flt

Action]

to the desired responses:

Changes to these parameters take effect immediately. A reset is not required.

If communication is disrupted and then re-established again, the drive will
automatically receive commands over the network again.

Setting the Fault Configuration Parameters

When setting

Device parameters 11 [Comm Flt Action] and 12 [Idle Flt

Action]

to 4 “Send Flt Cfg,” the values in the following parameters are sent to the

drive after a communications fault and/or idle fault for drive control occurs. You
must set these parameters to values required by your application.

Changes to these parameters take effect immediately. A reset is not required.

Resetting the Adapter

Changes to switch settings on some adapter parameters require that you reset the
adapter before the new settings take effect. You can reset the adapter by cycling
power to the drive or by using

Device parameter 19 [Reset Module].

Set

Device parameter 19 [Reset Module] to 1 “Reset Module”.

Value

Action

Description

0

Fault

The drive is faulted and stopped. Datalink data is no longer sent to the drive. (Default)

1

Stop

The drive is stopped as per Host parameter P045 [Stop Mode] setting. Datalink data sent to
the drive remains unchanged.

2

Zero Data

The drive is sent “0” values for all Reference and Datalink data. This does not command a stop.

3

Hold Last

The drive continues in its present state.

4

Send Flt Cfg

The drive is sent the Reference and Datalink data that you set in the fault configuration
parameters (Device parameters 13 [Flt Cfg Logic], 14 [Flt Cfg Ref], and 15 [Flt Cfg DL 1]
through 18 [Flt Cfg DL 4]).

Device Parameter

Description

13 [Flt Cfg Logic]

A 16-bit integer value sent to the drive for Logic Command.

14 [Flt Cfg Ref]

A 16-bit integer value sent to the drive for Reference.

15 [Flt Cfg DL 1] through
18 [Flt Cfg DL 4]

A 16-bit integer value sent to the drive for a Datalink.

ATTENTION: Risk of injury or equipment damage exists. If the adapter is
transmitting control I/O to the drive, the drive may fault when you reset the
adapter. Determine how your drive will respond before resetting the adapter.

Value

Description

0

Ready (Default)

1

Reset Module

2

Set Defaults