68

Rockwell Automation Publication 520COM-UM004A-EN-E - November 2013

Chapter 7

Using Multi-Drive Mode

For example, to access [Accel Time 1] (parameter P041 in PowerFlex 525 and
P109 in PowerFlex 4M) in each of the drives, the following slot and index values
would be used:

Drive 0 (PowerFlex 525) Slot = 1, Index = 41

Drive 1 (PowerFlex 4M) Slot = 5, Index = 109

Drive 2 (PowerFlex 4M) Slot = 9, Index = 109

Drive 3 (PowerFlex 4M) Slot = 13, Index = 109

Drive 4 (PowerFlex 4M) Slot = 17, Index = 109

Additional Information

When the PowerFlex 525 drive (Drive 0) is powered up, all configured
daisy-chained drives must be present before the 25-COMM-P adapter will
enter the Data Exchange mode. The PORT LED status indicator will flash
red while it is starting up.

If the PowerFlex 525 drive (Drive 0) is powered down, communications
with the four daisy-chained drives (Drive 1 to Drive 4) are disrupted and
the drives will take their corresponding Comm Loss Actions.

If any of the daisy-chained drives (Drive 1 to Drive 4) are powered down,
the respective Input Image (Logic Status and Feedback) will be set to zero.
Status information will not indicate there is a fault at the node, and the
I/O connection will not be dropped.