Using Multi-Drive Mode

Multi-Drive Example of I/O Image

Note:

If a daisy-chained drive is disconnected from the RS-485 (DSI) network

or powered down, the Logic Status and Feedback words for the affected drive will
be set to 0.

Configuring the RS-485
Network

The following parameters must be set in the daisy-chained PowerFlex 4M drives
and not in the master drive:

Note:

The RS-485 Multi-drive network is fixed at 19.2K baud rate, 8 data bits,

no parity, and 1 stop bit.

Controller

Scanner

Adapter

Word and I/O

PROFIBUS

DSI

Output
Image
(Write)

Input
Image
(Read)

Message
Handler

Message

Buffer

Logic Command

Word 0

Reference

Word 1

Drive 0

Logic Command

Word 2

Reference

Word 3

Logic Command

Word 4

Reference

Word 5

Logic Command

Word 6

Reference

Word 7

Logic Command

Word 8

Reference

Word 9

PowerFlex Drive 2

PowerFlex Drive 0

PowerFlex Drive 1

PowerFlex Drive 3

PowerFlex Drive 4

PowerFlex Drive 0

PowerFlex Drive 1

PowerFlex Drive 2

PowerFlex Drive 3

PowerFlex Drive 4

Drive 1

Drive 2

Drive 3

Drive 4

Logic Status

Word 0

Feedback

Word 1

Drive 0

Logic Status

Word 2

Feedback

Word 3

Logic Status

Word 4

Feedback

Word 5

Logic Status

Word 6

Feedback

Word 7

Logic Status

Word 8

Feedback

Word 9

Drive 1

Drive 2

Drive 3

Drive 4

Parameter

Value

P106 [Start Source]

5 “Comm Port”

P108 [Speed Reference]

5 “Comm Port”

C302 [Comm Data Rate]

4 “19.2K”

C303 [Comm Node Addr]

1...247 (must be unique)

C306 [Comm Format]

0 “RTU-8-N-1”