Overview, Chapter 2, Chapter – Rockwell Automation 440R Guardmaster EtherNet/IP Network Interface User Manual User Manual

Page 13

Advertising
background image

Rockwell Automation Publication 440R-UM009B-EN-P - February 2014

13

Chapter

2

Install a Guardmaster EtherNet/IP
Network Interface

Overview

This chapter describes how to physically install a Guardmaster EtherNet/IP
network interface; and how to mount the interface to DIN Rail.

This table lists where to find specific information.

Topic

Page

Installation Summary

14

Mount the Interface on a DIN Rail

15

Install the Interface

16

Wiring Requirements and Recommendations

16

Grounding Considerations

17

ATTENTION: Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC
60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may
not provide adequate protection to radio communication services in such
environments.
This equipment is supplied as open-type equipment. It must be mounted
within an enclosure that is suitably designed for those specific environmental
conditions that will be present and appropriately designed to prevent
personal injury resulting from accessibility to live parts. The enclosure must
have suitable flame-retardant properties to prevent or minimize the spread
of flame, complying with a flame spread rating of 5VA or be approved for the
application if nonmetallic. The interior of the enclosure must be accessible
only by the use of a tool. Subsequent sections of this publication may contain
additional information regarding specific enclosure type ratings that are
required to comply with certain product safety certifications.
In addition to this publication, see the following:

Industrial Automation Wiring and Grounding Guidelines, publication 1770-

4.1, for additional installation requirements

NEMA 250 and IEC 60529, as applicable, for explanations of the degrees of

protection provided by enclosures

Advertising