Install a Guardmaster EtherNet/IP Network Interface

Install the Interface

Install the interface to the left of Guardmaster Safety Relays equipped with an
optical communication bus. There must be no more than 5 mm horizontal
separation between two adjacent relays for the optical communication bus to
operate properly.

Wiring Requirements and Recommendations

Allow for at least 50 mm (2 in.) between I/O wiring ducts or terminal

strips and the interface.

Separate wiring by signal type. Bundle wiring with similar electrical

characteristics together.

Label wiring to all devices in the system. Use tape, shrink-tubing, or other

dependable means for labeling purposes. In addition to labeling, use
colored insulation to identify wiring based on signal characteristics. For
example, you may use blue for DC wiring and red for AC wiring.

Refer to the following illustration to wire the interface.

ATTENTION: Do not connect 120/240V AC power to the A1/A2 DC supply.

ATTENTION: Do not wire more than two conductors on any single terminal.

Table 1 - Wire Requirements

Wire Size

Type

Min

Max

440R- ENETR

Solid

0.14 mm

2

(26 AWG)

2.5 mm

2

(14 AWG)

Rated @ 90 ºC (194 ºF)
insulation max

Stranded

1.5 mm

2

(16 AWG)

A1 = Supply

A2 = Common

Ethernet
RJ-45
connector

TOP VIEW