Appendix D

Tag Definitions

Table 10 - GSR EM(D) NonRecoverableFault_A and NonRecoverableFault_B Fault Codes

Fault
Code

Description

Corrective Action

00H

No fault

None

01H

RAM test fault

Do one of the following:
Power cycle the safety relay.
Reconfigure the safety relay.
Validate the electrical installation and appropriate

measures to reduce noise and suppress surges are taken.

If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

02H

Stack over-/under-flow

03H

Configuration mismatch between
Processors A and B

04H

Internal timing fault

05H

EEPROM read/write failure

06H

B1 configuration fault

Do one of the following:
Check the wiring to terminal B1.
Reconfigure the safety relay.
Validate the electrical installation and appropriate

measures to reduce noise and suppress surges are taken.

If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

07H

Mismatch between current switch
settings (switch 1: Range) and setting
stored during power-up.

Do one of the following:
Change the switch settings to the correct values.
Power cycle the safety relay.
Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

08H

Mismatch between current switch
settings (switch 2: Time) and setting
stored during power-up.

09H

SPI compare fault

Do one of the following:
Power cycle the safety relay.
Reconfigure the safety relay.
Validate the electrical installation and appropriate

measures to reduce noise and suppress surges are taken.

If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

0BH

ROM test failure

11H

Pulse test fault on main transistor

Do one of the following:
Check wiring for shorts to 24V or other channels.
Power cycle the safety relay.
Reconfigure the safety relay.
Validate the electrical installation and appropriate

measures to reduce noise and suppress surges are taken.

If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

12H

Pulse test fault of transistor for safety
output channel 1

13H

Pulse test fault of transistor for safety
output channel 2