Rockwell Automation Publication 440R-UM009B-EN-P - February 2014

53

Tag Definitions

Appendix D

06H

Safety mat wiring detected on one of
the input pairs while the safety relay is
configured for ‘OR’ logic

Do one of the following:
If there are no safety mats, check the input wiring (safety

mat wiring is crossed from normal dual-channel device
wiring)

Change the safety relay to ‘AND’ logic.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

07H

Mismatch between current switch
settings and setting stored during
power-up

Do one of the following:
Change the switch settings to the correct values.
Power cycle the safety relay.
Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

09H

SPI compare fault

Do one of the following:
Power cycle the safety relay.
Reconfigure the safety relay.
Validate the electrical installation and appropriate

measures to reduce noise and suppress surges are taken.

If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

0BH

ROM test failure

0CH

Terminal S12 hardware input fault

0DH

Terminal S22 hardware input fault

0EH

Terminal S32 hardware input fault

0FH

Terminal S42 hardware input fault

10H

Terminal S34 hardware input fault

11H

Pulse test fault on main transistor

Do one of the following:
Check wiring for shorts to 24V or other channels.
Power cycle the safety relay.
Reconfigure the safety relay.
Validate the electrical installation and appropriate

measures to reduce noise and suppress surges are taken.

If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

12H

Pulse test fault of transistor for safety
output channel 1

13H

Pulse test fault of transistor for safety
output channel 2

14H-1EH

Internal plausibility test fault

Do one of the following:
Power cycle the safety relay.
Reconfigure the safety relay.
Validate the electrical installation and appropriate

measures to reduce noise and suppress surges are taken.

If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

1FH

Different Single Wire Safety input signal
detected at Processor A than Processor B

20H, 21H

Internal program fault

22H, 23H

Rotary switch read error

24H

Cross fault at processor pins for safety
outputs

25H

Under voltage detected

Do one of the following:
Validate the electrical installation and appropriate supply

voltage is provided.

Power cycle the safety relay.
Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

26H

Fault detected in the other Processor

If viewing the NonrecoverableFault_A tag, refer to
NonrecoverableFault_B tag.
If viewing NonrecoverableFault_B tag refer to
NonrecoverableFault_A tag.

Table 7 - GSR DI(S) NonRecoverableFault_A and NonRecoverableFault_B Fault Codes

Fault
Code

Description

Corrective Action