Chapter 5

Troubleshoot the Interface

Table 2 - Status Indicators for 440R-ENETR Interface

Status

Description

Module status

Off

No power applied to device

Solid green

Device operating normally

Flashing green

Device needs commissioning due to missing, incomplete, or incorrect configuration.

Flashing red/green

Module self-test

Flashing red

Recoverable fault.
Complete firmware update, verify address switches. Check for monitored safety relay fault.

Solid red

Unrecoverable fault, may require device replacement.

Network status

Off

Device is not online
- Device has not completed Dup_MAC_ID test.
- Device not powered - check module status indicator.

Flashing green

Device is online but has no CIP connections in the established state.

Solid green

Device online and has CIP connections in the established state.

Flashing red

One or more CIP connections in timed-out state.
Check for Guardmaster safety relay failure and controller operation.

Solid red

Duplicate IP address detected.
Verify IP address setting and correct, as needed.

Link 1 or Link 2 Activity / Status

Off

No link established.

Solid green

One of the following conditions exist:
A 100 Mbps (full or half duplex) link exists.
The ring network is operating normally.

Flashing green

Transmit or receive activity present on indicated port @ 100 Mbps.

Solid yellow

One of the following conditions exist:
A 10 Mbps (full or half duplex) link exists.
The ring network is operating normally.

Flashing yellow

Transmit or receive activity present on indicated port @ 10 Mbps.