60

Rockwell Automation Publication 440R-UM009B-EN-P - February 2014

Appendix D

Tag Definitions

Table 12 - GSR GLP NonRecoverableFault_A and NonRecoverableFault_B Fault Codes

Fault
Code

Description

Corrective Action

00H

No fault

None

03H

Jitter fault

04H

Proximity Sensor 1 (P12) stuck at High
fault: Potential damage or
misalignment of the Proximity Sensor
(e.g. exceeding maximum sensing
distance, both sensors detecting a
space).

Do one of the following:
• Check the alignment and functionality of the Proximity

Sensor.

• Power cycle the safety relay.
• Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

04H

Proximity Sensor 2 (P22) stuck at High
fault.

06H

Proximity Sensors cross fault.

Do one of the following:
• Check connection of P12 and P22 against shorts to 24V or

0V and cross loop shorts.

• Power cycle the safety relay.
• Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

07H

Self test of terminal 51 failed.

Do one of the following:
• Check connection of 51 or L61 against shorts to 24V or 0V

and cross loop shorts.

• Power cycle the safety relay.
• Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

08H

Self test of terminal L61 failed.

09H

Proximity Input Fault: Both Proximity
inputs are Low simultaneously.

Do one of the following:
• Check the alignment and functionality of the Proximity

Sensors.

• Power cycle the safety relay.
• Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

0AH

Proximity Input Fault: Both Proximity
inputs stuck at HIGH simultaneously.

0BH

SPI compare fault

0CH

Self test of Single Wire Safety outputs
L11, L61 fault

Do one of the following:
• Check connection of L11 or L61 against shorts to 24V or 0V

and cross loop shorts.

• Power cycle the safety relay.
• Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

0DH

Current configuration does not agree
with the safety relay memory:
• Switch settings do not match

required initial configuration or

• X14 and X24 are connected to inputs

S12, S22 but they are configured as
safety outputs or

• L1 and 51 connection has changed

after configuration

Do one of the following:
• Change the switch settings to the correct values.
• Power cycle the safety relay.
• Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support