Appendix D

Tag Definitions

Table 12 - GSR GLP NonRecoverableFault_A and NonRecoverableFault_B Fault Codes

Fault
Code

Description

Corrective Action

00H

No fault

None

03H

Jitter fault

04H

Proximity Sensor 1 (P12) stuck at High
fault: Potential damage or
misalignment of the Proximity Sensor
(e.g. exceeding maximum sensing
distance, both sensors detecting a
space).

Do one of the following:
Check the alignment and functionality of the Proximity

Sensor.

Power cycle the safety relay.
Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

04H

Proximity Sensor 2 (P22) stuck at High
fault.

06H

Proximity Sensors cross fault.

Do one of the following:
Check connection of P12 and P22 against shorts to 24V or

0V and cross loop shorts.

Power cycle the safety relay.
Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

07H

Self test of terminal 51 failed.

Do one of the following:
Check connection of 51 or L61 against shorts to 24V or 0V

and cross loop shorts.

Power cycle the safety relay.
Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

08H

Self test of terminal L61 failed.

09H

Proximity Input Fault: Both Proximity
inputs are Low simultaneously.

Do one of the following:
Check the alignment and functionality of the Proximity

Sensors.

Power cycle the safety relay.
Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

0AH

Proximity Input Fault: Both Proximity
inputs stuck at HIGH simultaneously.

0BH

SPI compare fault

0CH

Self test of Single Wire Safety outputs
L11, L61 fault

Do one of the following:
Check connection of L11 or L61 against shorts to 24V or 0V

and cross loop shorts.

Power cycle the safety relay.
Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

0DH

Current configuration does not agree
with the safety relay memory:
Switch settings do not match

required initial configuration or

X14 and X24 are connected to inputs

S12, S22 but they are configured as
safety outputs or

L1 and 51 connection has changed

after configuration

Do one of the following:
Change the switch settings to the correct values.
Power cycle the safety relay.
Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support