Tag Definitions

Appendix D

0EH

Mismatch between current switch
settings and setting stored during
power-up.

Do one of the following:
Change the switch settings to the correct values.
Power cycle the safety relay.
Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

0FH

EEPROM read/write failure

Do one of the following:
Change the switch settings to the correct values.
Power cycle the safety relay.
Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

11H

Compare State Fault

13H

L52 Fault

16H

Cross Tran Fault

18H

Gate Open Fault: Indicates the Gate
inputs, S12, S22, unexpectedly opened.

19H

Over Speed 1

1EH

Terminal S12 hardware input fault

1FH

Terminal S22 hardware input fault

20H

Pulse test fault on main transistor

Do one of the following:
Check wiring for shorts to 24V or other channels.
Power cycle the safety relay.
Reconfigure the safety relay.
Validate the electrical installation and appropriate

measures to reduce noise and suppress surges are taken.

If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

21H

Over voltage detected

Do one of the following:
Validate the electrical installation and appropriate supply

voltage is provided.

Power cycle the safety relay.
Reconfigure the safety relay.
If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

22H

S54_S54 Autostart fault

28H-39H

Rom Fault

Do one of the following:
Power cycle the safety relay.
Reconfigure the safety relay.
Validate the electrical installation and appropriate

measures to reduce noise and suppress surges are taken.

If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

Table 12 - GSR GLP NonRecoverableFault_A and NonRecoverableFault_B Fault Codes

Fault
Code

Description

Corrective Action