Rockwell Automation 440R Guardmaster EtherNet/IP Network Interface User Manual User Manual

Page 52

Advertising
background image

52

Rockwell Automation Publication 440R-UM009B-EN-P - February 2014

Appendix D

Tag Definitions

Slotx_GSR_DIS_S42

BOOL

S42 Status – Indicates whether terminal S42 of circuit IN02
is On or Off.
0 = The terminal is Off.
1 = The terminal is On.

Slotx_GSR_DIS_L12

BOOL

L12 Status – Indicates whether terminal L12 is On or Off.
0 = The terminal is Off.
1 = The terminal is On.

Slotx_GSR_DIS_S34

BOOL

S34 Status – Indicates whether terminal S34 is On or Off.
0 = The terminal is Off.
1 = The terminal is On.

Slotx_GSR_DIS_NonRecoverableFault_A

SINT

Non-Recoverable Fault Processor A – Indicates a
non­recoverable fault has been recorded by Safety Processor
A. See

Table 7 on page 52

for a list of non-recoverable fault

codes.

Slotx_GSR_DIS_NonRecoverableFault_B

SINT

Non-Recoverable Fault Processor B – Indicates a
non­recoverable fault has been recorded by Safety Processor
B. See

Table 7 on page 52

for a list of non-recoverable fault

codes.

Slotx_GSR_DIS_S12OpenWire

BOOL

S12 Open Wire - Indicates S12 open (0) and closed (1)
while S22 remained closed (1).

Slotx_GSR_DIS_S22OpenWire

BOOL

S22 Open Wire - Indicates S22 open (0) and closed (1)
while S12 remained closed (1).

Slotx_GSR_DIS_S32OpenWire

BOOL

S32 Open Wire - Indicates S32 open (0) and closed (1)
while S42 remained closed (1).

Slotx_GSR_DIS_S42OpenWire

BOOL

S42 Open Wire - Indicates S42 open (0) and closed (1)
while S32 remained closed (1).

Slotx_GSR_DIS_CrossLoopFault

BOOL

Cross Loop Fault – Indicates whether the safety relay has
detected a cross loop fault on one of the input circuits.
0 = No fault
1 = Cross loop fault

Slotx_GSR_DIS_InvalidSwitchSetting

BOOL

Invalid Switch Settings – Indicates the switch settings
changed after power-up of the safety relay.
0 = No fault
1 = Fault

Slotx_GSR_DIS_ResetHeldOn

BOOL

Reset Held On Fault – Indicates the reset signal On (1) for
longer than the maximum time of 3000 ms.
0 = No fault
1 = Fault

Table 7 - GSR DI(S) NonRecoverableFault_A and NonRecoverableFault_B Fault Codes

Fault
Code

Description

Corrective Action

00H

No fault

None

01H

RAM test fault

Do one of the following:
Power cycle the safety relay.
Reconfigure the safety relay.
Validate the electrical installation and appropriate

measures to reduce noise and suppress surges are taken.

If the fault persists, contact your local Rockwell Automation
technical support representative. For contact information, see:

http://rockwellautomation.com/support

02H

Stack over-/under-flow

03H

Configuration mismatch between
Processors A and B

04H

Internal timing fault

05H

EEPROM read/write failure

Table 6 - GSR DI(S) Module Input Tags