Introducing Block I/O

Chapter 1

1-4

Discrete transfer (Figure 1.3) is intended to be used with controllers which
do not have block transfer capability. However, discrete transfer can be
used with any PLC family controller. When using discrete transfer, the
block looks like a 1/2 I/O rack to the controller (four words of input image
table memory and four words of output image table memory). Note that
certain alarms and user scaling features are not available when using
discrete transfer.

Figure 1.3

Block I/O Connection in an SLC System using discrete transfer

Blocks are daisyĆchained to

a scanner

1747ĆSN Remote I/O

Scanner Module

10828ĆI

= 1 I/O Rack

Block I/O Ć each block

is 1/2 I/O rack

+

1/2

1/2

A simplified schematic of the input circuit of one input channel is
shown below.

RET in0

Simplified Schematic

1

1

inV0

inI0

GND in0

A/D

20M

249

20M

Analog Multiplexer

Instrumentation

Amplifier

Channel 0

Channel 1
Channel 2
Channel 3

Channel 0 Input

+

-

12501-I

Analog Input

Common

ATTENTION: The 249 ohm

input current shunt is rated at

0.25 Watts. Do not exceed this

power rating or apply more

than 6V across the resistor

Analog Input

Common

Inputs have selectable input ranges as shown below.

Application

Input Range Resolution

voltage

+10V

14 Bits

voltage or current

+5V

14 Bits

voltage

0 to 10V

14 Bits

voltage or current

0 to 5V

14 Bits

Inputs