Module Calibration

Chapter 7

7-3

Table 7.D

Calibration Block Transfer Read or Discrete Input Bit/Word Descriptions

Word

Decimal Bit

(Octal Bit)

Description

Bit 00

Input calibration error bit. When set, indicates input channel 0

calibration error.

Bit 01

Input calibration error bit. When set, indicates input channel 1

calibration error.

Bit 02

Input calibration error bit. When set, indicates input channel 2

calibration error.

Bit 03

Input calibration error bit. When set, indicates input channel 3

calibration error.

Bit 04

Output calibration error bit. When set, indicates output channel 0

calibration error.

Bit 05

Output calibration error bit. When set, indicates output channel 1

calibration error.

Word 0

Bit 06

High/Low bit HL. Indicates whether full scale or zero data point is

being updated:

Bit 6 = 1 - full scale

Bit 6 = 0 - zero data point

Bit 07

Calibration Done bit DN. When set (1), indicates calibration started

and selected channels updated.

Bit 08 (10)

Input Mode bit IM.

Bit 8 = 0 - Use for voltage inputs. Input scaling in mV

Bit 8 = 1 - Use for current inputs. Input scaling in

µ

A

Bits 09Ć10 (11Ć12) Not used.

Bit 11 (13)

EEPROM OK bit (OK). When set, indicates the calibration data has

been saved.

Bits 12Ć15 (14Ć17) Calibration mode bits. Indicates the calibration sequence is selected.

Word 1

Bits 00Ć15 (00Ć17) Corrected Input Data for Channel 0 using most recent calibration data.

Word 2

Bits 00Ć15 (00Ć17) Corrected Input Data for Channel 1 using most recent calibration data.

Word 3

Bits 00Ć15 (00Ć17) Corrected Input Data for Channel 2 using most recent calibration data.

Word 4

Bits 00Ć15 (00Ć17) Corrected Input Data for Channel 3 using most recent calibration data.