Introducing Block I/O

Chapter 1

1-10

You can choose one of three scaling methods:

binary counts
default scaling
user scaling

User scaling is not available when you select discrete transfer mode.

The following table shows the output signals produced by various module
data values entered in each of the three scaling methods. In the user scaling
column, S

max

was set to 5000 and S

min

was set to 0000.

Module Data

Output Signal

Binary Counts

Scaling

Default

Scaling

User

Scaling

Approx. +10.25V

8395

10250

5062

+10V

8191

10000

5000 (Smax)

0.000V

0000

00000

2500

-10.00V

-8192

-10000

0000 (Smin)

Approx. -10.25V

-8396

-10250

-0062

Current Outputs - 1791ĆN4C2 and 1791ĆNDC

A simplified schematic of a 0 to 20mA output channel is shown below.

2

Opto

Isolation

DAC

Digital

Output

I

OUTS

I

OUT

I

RET

2

Note: Schematic does not show overvoltage protection circuits.

High Side

Current

Monitor

-15V

+15V

12505-I

Isolated Analog

Output Common

Isolated Analog

Output Common

The 0 to 20mA output provides 13 bits of resolution and is capable of
driving loads as large as 1k ohm.