Chapter 2

2-15

Certain products are not compatible with extended node capabilities
obtained with the use of 82 ohm terminators. Table 2.G lists those products
that are not compatible.

Table 2.G

NonĆcompatible Products

Device

Series

Scanners Ć

1771ĆSN

All

1772ĆSD

All

1772ĆSD2

All

1775ĆSR

All

1775ĆS4A

All

1775ĆS4B

All

Adapters Ć

1771ĆAS

All

1771ĆASB

Series A

1771ĆDCM

All

Miscellaneous Ć

1771ĆAF

All

1771ĆAF1

All

The remote I/O link can operate at three speeds: 57.6K, 115.2K or 230.4K
bits/s. The selection of link speed is dependent on the scanner/processor
used, throughput requirements, distance required and the type of remote
I/O devices being used.

Throughput Requirements

Block throughput using analog block is dependent on the controllers data
transfer rate. Analog block outputs are updated within 10ms of receiving
output data from the controller. The analog block inputs are sampled in a
“round robin” fashion with an input channel sampled every 27ms. This
means that a given input channel is sampled every 108ms (four input
channels times 27ms). At the end of every sample period of 27ms, the most
recent input data is made available for data transfer to the controller.

Consult your programmable controller user manual for Remote I/O
Communications to determine your system throughput.

Compatibility of 1771 I/O

Products with Extended

Node Numbers

Selecting Remote I/O

Link Speed