Rockwell Automation 1791-XXXX ANALOG BLOCK I/O User Manual

Page 28

Advertising
background image

Installing Block I/O

Chapter 2

2-10

Table 2.C

Wiring Block Designations for Cat. No. 1791ĆNDV

Connections

1791-NDV

Connections

Designation

Description

Terminal No.

Power

+24

+24V dc Power

1

Power

Connections

RET +24

dc Return

3

GND

Chassis ground

2

1

Transducer

Power

2

+24V

For current input only

25

Remote I/O

BLU

Blue wire - RIO

6

Remote I/O

Connections

CLR

Clear wire - RIO

8

SHD

Shield - RIO

7

I/O Connections

inV0 thru inV3

Voltage Input 0 through 3

9, 13, 17, 21

Voltage Input

RET in0 thru

RET in3

Input Return 0 through 3

10, 14, 18, 22

inI0 thru inI3

Current Input 0 through 3

11, 15, 19, 23

Current Input

RET in0 thru

RET in3

Input Return 0 through 3

10, 14, 18, 22

Input Ground

GNDin0-GNDin3

Channels 0-3 ground

12, 16, 20, 24

3

Output

out 0 - RET out 0

Output 0 (+)

Return output 0 (-)

27

26

4

Output

out 1 - RET out 1

Output 1 (+)

Return output 1 (-)

29

28

4

Not used

For internal test only; not

for customer use.

4, 5, 30

1 Connect chassis ground to equipment grounding stud. These are not internally connected.

2

20Ć28V dc (nominal 24V, 100mA) voltage source for accommodating loopĆpowered current transducer inputs.

3 Terminals 12, 16, 20, and 24 are internally connected.

4

Terminals 26 and 28 internally connected together.

Advertising