Installing Block I/O

Chapter 2

2-7

Figure 2.7

Wiring Connections for the 120V ac Analog Block with Current Input and

CustomerĆSupplied Loop Power

RIO

1

30

L2/N

L1

L1

GND

N

NOT

USED

NOT

USED

BLU

SHD

in V0

CLR

in I0

in V1

+24

Vdc

RET

in0

GND

in0

RET

in1

GND

in1
RET

in2

GND

in2

RET

in3

GND

in3

RET

out0

RET

out1

in I1

in V2

in I2
in V3

in I3

out0

out1

NOT

USED

User Analog

Input Device

+

-

User Analog

Output Device

+

-

User +24V User GND

Analog signals must be within the

10V common mode voltage range

which is referenced to the analog

input common (GND). Typically, this

is accomplished by connecting to

user ground. If an input channel

floats outside of this range, invalid

input readings will result.

Current Input

Output

ATTENTION: The 249 ohm

input current shunt is rated

at 0.25 Watts. Do not

exceed this rating.

Figure 2.8

Wiring Connections for the 24V dc Analog Block with Current Input and

CustomerĆSupplied Loop Power

RIO

1

30

+24

GND

RET

+24

NOT

USED

NOT

USED

BLU

SHD

in V0

CLR

in I0

in V1

+24

Vdc

RET

in0

GND

in0

RET

in1

GND

in1
RET

in2

GND

in2

RET

in3

GND

in3

RET

out0

RET

out1

in I1

in V2

in I2
in V3

in I3

out0

out1

NOT

USED

User Analog

Input Device

+

-

User Analog

Output Device

+

-

User +24V User GND

Current Input

Output

ATTENTION: The 249 ohm

input current shunt is rated

at 0.25 Watts. Do not

exceed this rating.

+24V dc

Supply

+

-

Analog signals must be within the

10V common mode voltage range

which is referenced to the analog

input common (GND). Typically,

this is accomplished by connecting

to user ground. If an input channel

floats outside of this range, invalid

input readings will result.