Rockwell Automation 1791-XXXX ANALOG BLOCK I/O User Manual

Page 50

Advertising
background image

Analog Block Applications Using

Discrete Transfers

Chapter 5

5-4

Table 5.C

Filter Time Selection

Filter Time

Bit Settings

Filter Time

Bit 03 Bit 02 Bit 01 Bit 00

Default - no filter

0

0

0

0

Do not use.

0

0

0

1

200ms

0

0

1

0

300ms

0

0

1

1

400ms

0

1

0

0

500ms

0

1

0

1

600ms

0

1

1

0

700ms

0

1

1

1

800ms

1

0

0

0

900ms

1

0

0

1

1000ms

1

0

1

0

1100ms

1

0

1

1

1200ms

1

1

0

0

1300ms

1

1

0

1

1400ms

1

1

1

0

1500ms

1

1

1

1