Installing Block I/O

Chapter 2

2-3

Maximum

Network Distance

Baud Rate

Used

Maximum Capacity

and

When using

16 blocks/channel, 32

blocks/scanner (128 blocks with 4

57.6K

10,000 cableĆfeet

PLC 5/250

i

blocks/scanner, (128 blocks with 4

scanners) with 150 ohm terminator

115.2K

5,000 cableĆfeet

PLCĆ5 family (continued)

PLCĆ5/250 Ć requires

a 5150ĆRS remote scanner

32 blocks/channel, 32

57.6K

10,000 cableĆfeet

a 5 50 S e o e sca e

32 blocks/channel, 32

blocks/scanner, (128 blocks with 4

scanners) with 82 ohm terminator

115.2K

5,000 cableĆfeet

scanners) with 82 ohm terminator

and extended node addressing

230.4K

2,500 cableĆfeet

S C /

S

/O S

8 blocks with 150 ohm terminator

3

57.6K

10,000 cableĆfeet

SLCĆ5/02 (and greater)

Controller

1747ĆSN Remote I/O Scanner

Module (discrete mode only)

8 blocks with 150 ohm terminator

3

115.2K

5,000 cableĆfeet

Controller

Module (discrete mode only)

8 blocks with 82 ohm terminator

3

230.4K

2,500 cableĆfeet

1

PLCĆ5/15 series A and PLCĆ5/15 series B prior to revision H (B/H) can only address 3 blocks.

2

PLCĆ5/25 revisions prior to A/D can only address 7 blocks.

3

Analog block is 1/2 rack in discrete transfer mode. If you combine analog block and discrete transfer on the same RIO link, the capacity ranges between 8 and 15 blocks.

Figure 2.1 shows the mounting dimensions for the block I/O module.
Mount the blocks vertically with a minimum of 2” between blocks. This air
gap is necessary to maintain proper cooling air flow through the block.

Figure 2.1

Mounting Dimensions for the Block I/O Modules (1791ĆN4V2 shown)

2 mounting holes

for 1/4Ćinch screws

1

30

2.710

(68.8)

1.71

(43.4)

6.95

(176.5)

6.60

(167.6)

0.5

(12.7)

6.95H x 2.710W x 3.85D

(176.5H x 68.8W x 98D)

Inches

(Millimeters)

Equipment

Grounding

Stud

CAUTION: When tightening grounding stud nut, do not exceed 15 inĆlbs.

2.0 (50.8) air gap

on all 4 sides.

Block

Operating temperature in

air gap below module must

not exceed 60

o

C (140

o

F).

1791ĆN4V2

ANALOG BLOCK

POWER
COMM

FAULT

OUTPUT

INPUT

0

1

0
1

2
3

Installing the Block I/O