Module Calibration

Chapter 7

7-12

Calibration Example for the 1791ĆN4V2 Block I/O Module

The following example shows you how to calibrate the inputs and outputs
for the 1791-N4V2 block I/O module.

1.

For inputs – short all RET and GND together and short V

in

0 thru V

in

3

together. Connect voltage sources and meter between Vin and GND.
For outputs – connect meter and load to each output.

2.

Verify normal operation.

3.

Set the terminal radix to hexidecimal and set BTW word 0 to C03Fh.

4.

Set the voltage source to 0.000V and set the terminal radix to
decimal. Enter the output meter reading in BTW words 1 and 2.

5.

Set the terminal radix to hexidecimal and set BTW word 0 to C0BFh.

6.

Set BTW word 0 to C07Fh.

7.

Set the voltage source to 10.000V and set the terminal radix to
decimal. Enter the output meter reading in BTW words 1 and 2.

8.

Set the terminal radix to hexidecimal and set BTW word 0 to C0FFh.

9.

Set the terminal radix to decimal and verify module operation.

10.

Set the terminal radix to hexidecimal and set BTW word 0 to C8FFh.

11.

Return to normal default operation by setting BTW word 0 to 0800h.