Outputs – Rockwell Automation 1791-XXXX ANALOG BLOCK I/O User Manual

Page 15

Advertising
background image

Introducing Block I/O

Chapter 1

1-8

User Scaling

User scaling is available only when using the block transfer mode. This
mode allows you to define S

max

and S

min

in engineering units in the block

transfer write data table. The integer range is 32,767 to –32,768.

Important: If the range of user scaling values is set less than the range of
binary counts scaling values, input resolution is sacrificed.

Scaling Example

Using the +10V range scale, the following illustration shows five possible
input signals.

14 Bits

13.96 Bits

Nominal Range

10.25 10

0

-10 -10.25

Resolution

Input Signal

Margin

Margin

The following table shows how the five signals will be scaled using each
of the three scaling methods. In the user scaling column, the S

max

was set

to represent 5000 and the S

min

was set to represent 0.

I

t V l

Scaling Method

Input Value

Binary Counts

Default

User

Approx. +10.25V

8395

10250

5062

+10.000V

8191

10000

5000 (Smax)

0.000V

0000

00000

2500

-10.000V

-8192

-10000

0000 (Smin)

Approx. -10.25V

-8396

-10250

-0062

The type of output your block I/O module has depends on its catalog
number:

1791-N4V2 and 1791-NDV have two +10V voltage outputs
1791-N4C2 and 1791-NDC have two 0-20mA current outputs

For any of the above modules, if your program tries to write a value which
is outside the output range, the output will be clamped at either the
maximum or minimum value. This condition will be indicated in the block
transfer read status word.

Outputs

Advertising