Installing block i/o chapter 2 – Rockwell Automation 1791-XXXX ANALOG BLOCK I/O User Manual

Page 26

Advertising
background image

Installing Block I/O

Chapter 2

2-8

Figure 2.9

Wiring Connections for the 120V ac Analog Block with Current Input and

BlockĆSupplied Loop Power

RIO

1

30

L2/N

L1

L1

GND

N

NOT

USED

NOT

USED

BLU

SHD

in V0

CLR

in I0

in V1

+24

Vdc

RET

in0

GND

in0

RET

in1

GND

in1
RET

in2

GND

in2

RET

in3

GND

in3

RET

out0

RET

out1

in I1

in V2

in I2

in V3

in I3

out0

out1

NOT

USED

User Analog

Input Device

i

i

Loop Powered

Current Input

User Analog

Output Device

+

-

Output

ATTENTION: The 249 ohm

input current shunt is rated

at 0.25 Watts. Do not

exceed this rating.

Analog signals must be within the

10V common mode voltage range

which is referenced to the analog

input common (GND). Typically, this

is accomplished by connecting to

user ground. If an input channel

floats outside of this range, invalid

input readings will result.

+24V dc loop power supplied

at terminal 25 on block

Figure 2.10

Wiring Connections for the 24V dc Analog Block Module with Current

Input and BlockĆSupplied Loop Power

RIO

1

30

GND

NOT

USED

NOT

USED

BLU

SHD

in V0

CLR

in I0

in V1

+24

Vdc

RET

in0

GND

in0

RET

in1

GND

in1
RET

in2

GND

in2

RET

in3

GND

in3

RET

out0

RET

out1

in I1

in V2

in I2

in V3

in I3

out0

out1

NOT

USED

User Analog

Input Device

i

i

Loop Powered

Current Input

User Analog

Output Device

+

-

Output

ATTENTION: The 249 ohm

input current shunt is rated

at 0.25 Watts. Do not

exceed this rating.

+24

RET

+24

+24V dc

Supply

+

-

+24V dc loop power supplied

at terminal 25 on block

Analog signals must be within the

10V common mode voltage range

which is referenced to the analog

input common (GND). Typically, this

is accomplished by connecting to

user ground. If an input channel

floats outside of this range, invalid

input readings will result.