Module scan time – Rockwell Automation 1791-XXXX ANALOG BLOCK I/O User Manual

Page 40

Advertising
background image

Configuring Your Block I/O for PLC

Family Programmable Controllers

Chapter 3

3-7

Scan time depends on the block transfer rate over the remote I/O network,
which is asynchronous to the module input sample rate and output update
rate. The block transfer rate is dependent on the controller, program length,
the amount of communication traffic to other modules on the remote I/O
network and the speed (baud rate) of the remote I/O network.

Figure 3.4

Module Scan Time Relationships

Ch 0

Ch 1

Ch 2

Ch 3

Ch 0

Ch 1

Ch 2

Ch 3

Ch 0

Ch 1

100ms to 2s

1

Ch 0 & Ch 1

updated

BTW1

BTW2

Block Transfer

Read

Block Transfer

Write

Input Sample

Rate

Output Update

100ms to 2s

1

BTR1

BTR2

Ch 0 & Ch 1

updated

10ms

10ms

108ms

1

Time depends on the remote I/O network configuration.

Module Scan Time