Rockwell Automation 1791-XXXX ANALOG BLOCK I/O User Manual

Page 59

Advertising
background image

Module Calibration

Chapter 7

7-4

Table 7.E

Discrete Transfer Input Data File

Word/Bit

Description

0

Corrected Input Channel 0 Data

1

Corrected Input Channel 1 Data

2

Corrected Input Channel 2 Data

3

Corrected Input Channel 3 Data

Table 7.F

Discrete Transfer Input Bit/Word Descriptions

Word/Bit

Description

0

Corrected Input Data for Channel 0 using most recent calibration data.

1

Corrected Input Data for Channel 1 using most recent calibration data.

2

Corrected Input Data for Channel 2 using most recent calibration data.

3

Corrected Input Data for Channel 3 using most recent calibration data.

Calibrating Voltage Inputs

Use the procedure below to calibrate the voltage inputs on your analog
block I/O module. The procedure can be used for either PLC or SLC
systems.

You can calibrate any single input or output individually or, you can
calibrate them simultaneously.

Important: To allow the module to stabilize, energize the module for at
least 30 minutes before calibrating.

To calibrate your module:

1.

Connect your test equipment for the input you want to calibrate. This
is shown in the figure below.

V

IN

I

IN

RET

GND

0-10V Reference Source

V

V

R