Chapter 4

Analog Block Applications Using

Block Transfers

4-3

You must configure your block module by performing a block transfer
write (BTW) instruction from the programmable controller to the module.
Each input can be independently configured in one BTW.

Maximum length of the BTW is 27 words (0 thru 26). When configuring
the module, first send the complete BTW. You can shorten the BTW to 3
words for subsequent write operations if parameters for each channel
remain the same.

Block transfer write data is shown in Figure 4.2.

Figure 4.2

Block Transfer Write for Analog Block I/O

Decimal

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Octal

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

0

Module Mode

Scaling

Range

Alarm Enable

Filter

1

Output Channel 0 Data

2

Output Channel 1 Data

3

Output Channel 0 Minimum Scaling

4

Output Channel 0 Maximum Scaling

5

Output Channel 1 Minimum Scaling

6

Output Channel 1 Maximum Scaling

7

Input Channel 0 Minimum Scaling

8

Input Channel 0 Maximum Scaling

9

Input Channel 1 Minimum Scaling

10

Input Channel 1 Maximum Scaling

11

Input Channel 2 Minimum Scaling

12

Input Channel 2 Maximum Scaling

13

Input Channel 3 Minimum Scaling

14

Input Channel 3 Maximum Scaling

15

Input Channel 0 Low Alarm Level

16

Input Channel 0 High Alarm Level

17

Input Channel 0 Alarm Deadband

18

Input Channel 1 Low Alarm Level

19

Input Channel 1 High Alarm Level

20

Input Channel 1 Alarm Deadband

21

Input Channel 2 Low Alarm Level

22

Input Channel 2 High Alarm Level

23

Input Channel 2 Alarm Deadband

24

Input Channel 3 Low Alarm Level

25

Input Channel 3 High Alarm Level

26

Input Channel 3 Alarm Deadband

Configuring the Module and

Setting Outputs with Block

Transfer Write Instructions