Introducing Block I/O

Chapter 1

1-7

The following equation shows how the module interprets the input data:

Module data = M x V

in

+ B

where:

(S

max

– S

min

)

(V

nfs

– V

nbs

)

M =

(S

min

x V

nfs

) – (S

max

x V

nbs

)

(V

nfs

– V

nbs

)

B =

You can choose one of three scaling methods:

binary counts (module sets scalers)
default scaling (module sets scalers)
user scaling (you set scalers)

User scaling is not available when you select discrete transfer mode.

Binary Counts Scaling

Binary counts scaling mode activates when the module powers up. This
mode guarantees the maximum resolution. The module sets the scalers as
shown in the following table:

Scaler

+/-10V

0-10V

+/-5V

0-5V

S

max

8191

16383

8191

16383

S

min

-8192

0

-8192

0

Default Scaling

Default scaling mode scales inputs to the input stimulus in either millivolts
or microamps. The module sets the scalers as shown in the following
tables:

With Voltage Input Selected

Scaler

+/-10V

0-10V

+/-5V

0-5V

S

max

10,000mV

10,000mV

5000mV

5000mV

S

min

-10,000mV

0mV

-5000mV

0mV

With Current Input Selected

Scaler

+/-10V

0-10V

+/-5V

0-5V

S

max

N/A

N/A

20000uA

20000uA

S

min

N/A

N/A

-20000uA

0uA