Chapter 2

2-13

A termination resistor must be installed on the last block in a series.
Connect the resistor as shown in Figure 2.11.

Figure 2.11

Installing the Termination Resistor

Termination

Resistor

Connect termination resistor across

terminals 6 (BLU) and 8 (CLR).

10835ĆI

BLU

SHD

CLR

Refer to Table 2.A for proper

terminator for your application.

Blocks must be wired in series as shown in Figure 2.12 or Figure 2.13. Do
not attempt to wire any block in parallel.

The number of blocks used depends not only on the user requirements but
also on the system used. Refer to Table 2.A (page 2-1) for maximum
block usage for individual systems.

Figure 2.12

Series Connection for Block I/O Using PLCĆ2, PLCĆ3 or PLCĆ5 Family

Programmable Controllers

Install terminating resistor on last block.

To Programmable

Controller or I/O

Scanner Module

1 I/O Rack

1 I/O Rack

1 I/O Rack

1 I/O Rack

10833ĆI

Termination Resistor

Remote I/O Link