background image

16

Rockwell Automation Publication 1783-UM001D-EN-P - January 2013

Chapter 1

Basic Configuration

4. Type your new IP address.
5. Change the subnet mask and default gateway, if needed.
6. Turn off BOOTP Client to prevent dynamic IP address assignment.

If using host names on the network, Name Resolution must be turned on
and the DNS server addresses must be configured (usually required if using
the email function).

7. Click Apply Changes to change the IP and subnet.

8. Cycle power.

Once the IP and subnet are changed, you must cycle power to load the new
address. Power can be cycled remotely through the management interface
by expanding the Diagnostics folder and clicking Controller Restart. This
restarts the 1783-EMS switch and does not restart the controller. All
communication through the switch is interrupted.

IMPORTANT

The switch does not load the new IP and subnet address until
power is cycled.