Rockwell Automation 1783-EMS08T Stratix 6000 Ethernet Managed Switch User Manual User Manual

Page 24

Advertising
background image

24

Rockwell Automation Publication 1783-UM001D-EN-P - January 2013

Chapter 2

Network Services Setup

2. From the SNMP Enabled pull-down menu, choose Enabled to use SNMP.
3. Change the deault case-sensitive community names if desired.

The read-only community enables the switch to validate Get (read-

only) requests from a network management station. If you set the
SNMP read community, users can access MIB objects, but cannot
change them.

The read-write community enables the switch to validate Set (read-

write) requests from a network management station.

4. In the System Info area, provide optional information about the switch for

informational purposes only.
a. In the Location field, type the physical location of the switch, such as

the building where the switch is locatd.

b. In the Contact field, type the switch name or network administrator.

5. Identify up to two trap destinations by completing the fields below.

6. Click Apply Changes.

The changes will take effect immediately without requiring you to cycle
power to the switch.

Trap Destination Field

Description

Enabled

Check to enable trap messages to be sent.

IP Address

Type the IP address of the SNMP trap recipient.

Port

Type the UDP port number to which traps will be sent.
The default port number is 162.

Community

Type the read-only or read-write SNMP community name to be used in
traps sent to the destination.
Community names are case-sensitive.

SNMP Version

Choose the SNMP version to use.