Basic Configuration

Chapter 1

Table 3 - Miscellaneous Switch Settings

Setting

Description

Box Name

Lets you give your 1783-EMS switch a name that describes its location or connected devices. This feature is useful when multiple 1783-EMS
switches are installed. The switch reports this name on the home page. To change this setting, complete this procedure.
1. Click Basic Configuration.
2. Click Miscellaneous.
3. Type the new name in the text box and click Apply Changes.

The new name does not show in the home page until you click Refresh on the browser.

Minutes of User Inactivity

Lets you change the length of time the management interface (HTTP session) remains open while inactive. Choose from 0…99 min. Select
0 = Feature Disabled for the interface to remain open until it is closed. The default is 3 min.

Seconds Between Refresh

Controls the refresh rate of the management interface.
Valid values are 0…99 seconds
0 = Feature disabled for no refresh
Default value is 5 seconds

Contact Info, Contact Email

Use to identify the responsible service personnel.