Appendix B Configuring the 1769-IR6 RTD Module with the Generic Profile

Note the Assembly Instance numbers and their associated sizes for the 1769-
IR6 module and enter them into the Generic Profile. The Generic Profile for a
1769-IR6 should look like the following:

Click “Finish” to complete the configuration of your I/O module.

Configure each RTD Input module in this manner. The CompactLogix5320
controller supports a maximum of eight I/O modules. The valid slot numbers
to select when configuring I/O modules are 1…8.

Configuring I/O Modules

Once you have created a Generic Profile for the 1769-IR6 RTD Input module,
you must then enter configuration information into the Tag database that has
been automatically created from the Generic Profile information you entered.
This configuration information is then downloaded to each module at
program download, at power up and when an inhibited module is uninhibited.

This section shows how and where to enter configuration data for your IR6
module, once Generic Profiles have been created for them.

We must first enter the Controller Tag database, by double-clicking on
“Controller Tags” in the upper portion of the Controller Organizer.