Error Codes

The table below explains the extended error code.

Table 24 - Extended Error Codes

Error Type

Hex

Equivalent

(1)

Module

Error

Code

Extended Error

Information

Code

Error Description

Binary

Binary

No Error

X000

000

0 0000 0000

No Error

General Common
Hardware Error

X200

001

0 0000 0000

General hardware error; no additional information

X201

001

0 0000 0001

Power-up reset state

Hardware-
Specific Error

X300

001

1 0000 0000

General hardware error, loss of external 24V DC power

X301

001

1 0000 0001

Hardware ROM error

X302

001

1 0000 0010

Hardware EEPROM error

X303

001

1 0000 0011

Channel 0 calibration error

X304

001

1 0000 0100

Channel 1 calibration error

X305

001

1 0000 0101

Channel 2 calibration error

X306

001

1 0000 0110

Channel 3 calibration error

X307

001

1 0000 0111

Channel 4 calibration error

X308

001

1 0000 1000

Channel 5 calibration error

X309

001

1 0000 1001

Channel 0 Analog/Digital Converter error

X30A

001

1 0000 1010

Channel 1 Analog/Digital Converter error

X30B

001

1 0000 1011

Channel 2 Analog/Digital Converter error

X30C

001

1 0000 1100

Channel 3 Analog/Digital Converter error

X30D

001

1 0000 1101

Channel 4 Analog/Digital Converter error

X30E

001

1 0000 1110

Channel 5 Analog/Digital Converter error