Selecting Data Format (Bits 12…14)

Bits 12…14 of the channel configuration word are used to indicate the input
data format. You may choose any of the following formats:

·

raw/proportional

·

engineering units x 1

·

engineering units x 10

·

scaled for PID

·

percent of full scale

TIP

The engineering units data formats represent real
temperature or resistance engineering units provided by the
module. The raw/proportional counts, scaled-for-PID, and
percent of full scale data formats The raw/proportional
counts, scaled-for-PID and percent of full-scale data
formats may yield the highest effective resolutions, but may
also require that you convert channel data to real
engineering units in your control program.

Table 8 - Data Formats for RTD Temperature Ranges for 0.5 and 1.0 mA Excitation Current

RTD Input Type

Data Format

Engineering Units x1

Engineering Units x10

Scaled-for-PID

Proportional

Counts

0.1 °C

0.1 °F

1.0 °C

1.0 °F

100

Ω Platinum 385

-2000…8500

-3280…15620

-200…850

-328…1562

0…16383

-32768…32767

200

Ω Platinum 385

-2000…8500

-3280…15620

-200…850

-328…1562

0…16383

-32768…32767

500

Ω Platinum 385

-2000…8500

-3280…15620

-200…850

-328…1562

0…16383

-32768…32767

1000

Ω Platinum 385

-2000…8500

-3280…15620

-200…850

-328…1562

0…16383

-32768…32767

100

Ω Platinum 3916

-2000…6300

-3280…11660

-200…630

-328…1166

0…16383

-32768…32767

200

Ω Platinum 3916

-2000…6300

-3280…11660

-200…630

-328…1166

0…16383

-32768…32767

500

Ω Platinum 3916

-2000…6300

-3280…11660

-200…630

-328…1166

0…16383

-32768…32767

1000

Ω Platinum 3916 -2000…6300

-3280…11660

-200…630

-328…1166

0…16383

-32768…32767

10

Ω Copper 426

-1000…2600

-1480…5000

100…260

-148…500

0…16383

-32768…32767

120

Ω Nickel 618

-1000…2600

-1480…5000

-100…260

-148…500

0…16383

-32768…32767

120

Ω Nickel 672

-800…2600

-1120…5000

-80…260

-112…500

0…16383

-32768…32767

60

Ω Nickel Iron 518

-1000…2000

-3280…1560

-100…200

-328…156

0…16383

-32768…32767