Appendix A Module Addressing and Programming with MicroLogix 1500 and RSLogix 500

1769-IR6 Configuration File

The configuration file contains information you use to define the way a
specific channel functions. The configuration file is explained in more detail in
Configuring Channels on page 50.

The default configuration of the table is all zeros, which yields the following.

TIP

The end cap does not use a slot address.

Table 25 - Default Configuration

Parameter

Default Setting

Channel Enable/Disable

Disable

Input Type

100

Ω Platinum 385

Data Format

Raw/Proportional

Temperature Units

°C (not applicable with Raw/Proportional)

Broken Input

Upscale

Disable Cyclic Lead Compensation

Enable

Excitation Current

1.0 mA

Input FIlter Frequency

60 Hz

0

1

2

3

M

icr

oLog

ix 1

50

0

Compact I/O

Compact I/O

Compact I/O

En

d Ca

p

Slot Number