1769-ir6 configuration file – Rockwell Automation 1769-IR6 Compact I/O 1769-IR6 RTD/Resistance Input Module User Manual
Page 92

92
Rockwell Automation Publication 1769-UM005B-EN-P - March 2012
Appendix A Module Addressing and Programming with MicroLogix 1500 and RSLogix 500
1769-IR6 Configuration File
The configuration file contains information you use to define the way a
specific channel functions. The configuration file is explained in more detail in
Configuring Channels on page 50.
The default configuration of the table is all zeros, which yields the following.
TIP
The end cap does not use a slot address.
Table 25 - Default Configuration
Parameter
Default Setting
Channel Enable/Disable
Disable
Input Type
100
Ω Platinum 385
Data Format
Raw/Proportional
Temperature Units
°C (not applicable with Raw/Proportional)
Broken Input
Upscale
Disable Cyclic Lead Compensation
Enable
Excitation Current
1.0 mA
Input FIlter Frequency
60 Hz