Chapter 3 Installation and Wiring

Field Wiring Connections

System Wiring Guidelines

Consider the following when wiring your system:

General

·

This product is intended to be mounted to a well-grounded mounting
surface such as a metal panel. Additional grounding connections from
the module’s mounting tabs or DIN rail (if used) are not required unless
the mounting surface cannot be grounded.

·

Channels are isolated from one another by ±10V DC maximum.

·

Route field wiring away from any other wiring and as far as possible
from sources of electrical noise, such as motors, transformers,
contactors, and AC devices. As a general rule, allow at least 15.2 cm
(6 in.) of separation for every 120V of power.

·

Routing field wiring in a grounded conduit can reduce electrical noise.

·

If field wiring must cross AC or power cables, ensure that they cross at
right angles.

·

To ensure optimum accuracy, limit overall cable impedance by keeping
your cable as short as possible. Locate the I/O system as close to your
sensors or actuators as your application will permit.

·

Tighten terminal screws with care. Excessive tightening can strip a
screw.

Shield Grounding

·

Use Belden shielded, twisted-pair wire to ensure proper operation and
high immunity to electrical noise. Refer to the following table and the

RTD Wiring Considerations

below.

·

Under normal conditions, the drain wire and shield junction should be
connected to earth ground, via a panel or DIN rail mounting screw at
the 1769-IR6 module end.

·

Keep shield connection to ground as short as possible.

·

If noise persists for a device, try grounding the opposite end of the
cable. (You can only ground one end at a time.)

·

Refer to Industrial Automation Wiring and Grounding Guidelines,
publication

1770-4.1

, for additional information.

Configuration

Recommended Cable

2-wire

Belden 9501 or equivalent

3-wire
less than 30.48 m (100 ft)

Belden 9533 or equivalent

3-wire
greater than 30.48 m (100 ft) or high humidity conditions

Belden 83503 or equivalent