Module Data, Status, and Channel Configuration Chapter 4
Input Data File
The input data table lets you access RTD input module read data for use in the
control program, via word and bit access. The data table structure is shown in
table below.
Input Data Values
Data words 0…5 correspond to channels 0…5 and contain the converted
analog input data from the input device.
Table 4 - Input Data Table
Word/Bit
(1)
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
Analog Input Data Channel 0
1
Analog Input Data Channel 1
2
Analog Input Data Channel 2
3
Analog Input Data Channel 3
4
Analog Input Data Channel 4
5
Analog Input Data Channel 5
6
Not Used
OC5
OC4
OC3
OC2
OC1
OC0
Not Used
S5
S4
S3
S2
S1
S0
7
U0
O0
U1
O1
U2
O2
U3
O3
U4
O4
U5
O5
Not Used
(1) Modifying bit values is not supported by all controllers. Refer to your controller manual for details.
TIP
Status bits for a particular channel reflect the configuration
settings for that channel. To receive valid status, the
channel must be enabled and the module must have stored
a valid configuration word for that channel.