Rockwell Automation Publication 1769-UM005B-EN-P - March 2012

33

Installation and Wiring Chapter 3

8.

Lock the end cap bus terminator (6).

Mounting

Minimum Spacing

Maintain spacing from enclosure walls, wireways, and adjacent equipment.
Allow 50 mm (2 in.) of space on all sides for adequate ventilation, as shown
below:

IMPORTANT

A 1769-ECR or 1769-ECL right or left end cap
respectively must be used to terminate the end of the
bus.

ATTENTION:

During panel or DIN rail mounting of all

devices, be sure that all debris (metal chips, wire strands) is
kept from falling into the module. Debris that falls into the
module could cause damage at power up.

Host Controller

Compact I/O

Compact I/O

Compact I/O

Compact I/O

Compact I/O

En

d Ca

p

Side

Side

Top

Bottom