Chapter 2 Quick Start for Experienced Users

6.

Monitoring module operation

The modules maximum current draw is shown below.

(1) The system power supply could be a 1769-PA2, -PB2, -PA4, -PB4, or the internal power supply of a MicroLogix

1500 packaged controller.

.

Step 1:

Ensure that your 1769 system power supply

(1)

has sufficient current output to

support your system configuration.

Reference

Chapter 3
(Installation and Wiring)

5V DC

24V DC

100 mA

45 mA

TIP

The module cannot be located more than 8 modules away
from the 1769 system power supply.

Step 2:

Attach and lock the module.

Reference

Chapter 3
(Installation and Wiring)

TIP

The modules can be panel or DIN rail mounted. Modules
can be assembled before or after mounting.

ATTENTION:

Remove power before removing or

inserting this module. When you remove or insert a
module with power applied, an electrical arc may occur.