Wiring resistance devices (potentiometers) – Rockwell Automation 1769-IR6 Compact I/O 1769-IR6 RTD/Resistance Input Module User Manual
Page 42
![background image](/manuals/579602/42/background.png)
42
Rockwell Automation Publication 1769-UM005B-EN-P - March 2012
Chapter 3 Installation and Wiring
4-Wire RTD Configuration
Wiring Resistance Devices (Potentiometers)
Potentiometer wiring requires the same type of cable as that for the RTDs
described on page 3-37. Potentiometers can be connected to the module as a
2-wire or 3-wire connection as shown on page 3-42.
2-Wire Potentiometer Interconnection
TIP
The potentiometer wiper arm can be connected to either
the EXC or return terminal depending on whether you
want increasing or decreasing resistance.
EXC 3
SENSE 3
RTN 3
EXC 4
Belden 83503 or 9533 Shielded Cable
Leave one sensor wire open.
Cable Shield (to Ground)
RTD EXC
Return
RTD EXC
Return
Sense
Sense
EXC 3
SENSE 3
RTN 3
EXC 3
SENSE 3
RTN 3
Cable Shield (to Ground)
Potentiometer
RTD EXC
Return
Add Jumper
Cable Shield (to Ground)
Potentiometer
RTD EXC
Return
Add Jumper
Belden 9501 Shielded Cable
Belden 9501 Shielded Cable